Chapter 5 Parameters|VFD-B Series
FWD-DCM (close)
Pr.02-01=0
output frequency
Pr.02-06=2 or 3
Change operation
command source
output frequency
Pr.02-06=0 or 1
When the operation command source isn't from the external terminals, independently from
whether the AC motor drive runs or stops, the AC motor drive will operate according to Pr.02-
06 if the two conditions below are both met.
1.
When operation command source is changed to external terminal (Pr.02-01=1 or 2, Pr.02-
14=1 or 2)
2.
The status of terminal and AC motor drive is different.
And the operation of the AC motor drive will be:
1.
When setting 0 or 1, the status of AC motor drive is not changed by the terminal status.
2.
When setting 2 or 3, the status of AC motor drive is changed by the terminal status.
FWD-DCM (close)
power is applied
output frequency
Pr.02-06=0 or 2
output frequency
Pr.02-06=1 or 3
The Line Start Lockout feature does not guarantee that the motor will never start under this
condition. It is possible the motor may be set in motion by a malfunctioning switch.
5-40
ON
RUN
RUN
STOP
STOP
Pr.02-01=1 or 2
ON
OFF
ON
it will run
it won't run
when power is applied
OFF
This action will follow FWD/DCM
or REV/DCM status
(ON is close/OFF is open)
OFF
ON
It needs to received a run command
after previous command is cancelled
Revision July 2008, BE16, SW V4.08 & V5.00