B.7 Zero Phase Reactor (Rf220X00A) - Delta VFD-B User Manual

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

B.7 Zero Phase Reactor (RF220X00A)

Dimensions are in millimeter and (inch)
Recommended Wire
Cable
Size
type
(Note)
2
AWG mm
≦10 ≦5.3
Single-
core
≦2 ≦33.6
≦12 ≦3.3
Three-
core
≦1 ≦42.4
Note: 600V Insulated unshielded Cable.
Diagram A
Please wind each wire 4 times around the
core. The reactor must be put at inverter
output as close as possible.
R/L1
Power
S/L2
Supply
T/L3
W/T3
Revision July 2008, BE16, SW V4.08 & V5.00
Qty.
Method
Nominal
2
(mm
)
Diagram
1
≦5.5
Diagram
4
≦38
Diagram
1
≦3.5
Diagram
4
≦50
Zero Phase Reactor
U/T1
V/T2
Diagram B
Please put all wires through 4 cores in
Wiring
series without winding.
Power
Supply
A
B
Note 1: The table above gives approximate
wire size for the zero phase reactors but the
A
selection is ultimately governed by the type
and diameter of cable fitted i.e. the cable
must fit through the center hole of zero
B
phase reactors.
Note 2: Only the phase conductors should
pass through, not the earth core or screen.
Note 3: When long motor output cables are
used an output zero phase reactor may be
required to reduce radiated emissions from
the cable.
MOTOR
Appendix B Accessories|VFD-B Series
Zero Phase Reactor
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
MOTOR
B-37

Hide quick links:

Advertisement

Table of Contents
loading