Chapter 5 Parameters|VFD-B Series
This parameter is to delay the signals on digital input terminals. 1 unit is 2 msec, 2 units are 4
msec, etc. The delay time is used to debounce noisy signals that could cause the digital
terminals to malfunction.
04 - 23

Gear Ratio for Simple Index Function

Settings
04 - 24

Index Angle for Simple Index Function

Settings
04 - 25

Deceleration Time for Simple Index Function

Settings
The simple index function is used to position the machine/motor at the same position when it
stops. The function should be used with setting 34 for Multi-Function Input Terminals (04-04 to
04-09).
The function diagram is shown below. The machine is driven by a gear motor or other
reduction gearbox. The trigger position of the proximity sensor is used as the starting point of
the index angle. When the stop command is initiated, the AC motor drive will not decelerate
until the proximity sensor is triggered. After that the AC motor drive begins to decelerate and
stop according to the Pr.04-24 and Pr.04-25.
Frequency
5-58
4 ~ 1000
0.0 ~360.0°
0.00 ~100.00 sec
time between STOP and triggering by proximity
sensor. It depends on the moment the STOP
Signal of Zero
command is given.
=Pr.04-25
Proximity Sensor Actives
Time
Revision July 2008, BE16, SW V4.08 & V5.00
Unit: 1
Factory Setting: 200
Unit: 0.1
Factory Setting: 180.0
Unit: 0.01
Factory Setting: 0.00