Jog Acceleration Time; Jog Deceleration Time; Jog Frequency; Auto-Acceleration/Deceleration - Delta VFD-B User Manual

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

Chapter 5 Parameters|VFD-B Series
01 - 13

Jog Acceleration Time

Settings
01 - 22

Jog Deceleration Time

Settings
01 - 14

Jog Frequency

Settings
Both external terminal JOG and key "JOG" on the keypad can be used. When the Jog
command is "ON", the AC motor drive will accelerate from Minimum Output Frequency (Pr.01-
05) to Jog Frequency (Pr.01-14). When the Jog command is "OFF", the AC motor drive will
decelerate from Jog Frequency to zero. The used Accel/Decel time is set by the Jog
Accel/Decel time (Pr.01-13, Pr.01-22).
Before using the JOG command, the drive must be stopped first. And during Jog operation,
other operation commands cannot be accepted, except command via the FORWARD,
REVERSE and STOP keys on the digital keypad.
Frequency
01-14
JOG
Frequency
01-05
Min. output
frequency
0 Hz
01 -15
Auto-Acceleration / Deceleration
Settings
5-32
0.1 to 3600.0 sec
0.1 to 3600.0 sec
0.10 to 400.00Hz
JOG Accel. Time
01-13
The definition of JOG Accel./Decel. Time
00
Linear acceleration / deceleration
01
Auto acceleration, linear Deceleration.
02
Linear acceleration, auto Deceleration.
03
Auto acceleration / deceleration (set by load)
04
Auto acceleration / deceleration (set by Accel/Decel Time setting)
Factory Setting: 1.0
Factory Setting: 1.0
Factory Setting: 1.0
JOG Decel. Time
01-22
Factory Setting: 00
Revision July 2008, BE16, SW V4.08 & V5.00
Unit: 0.1
Unit: 0.1
Unit: 0.1
Time