Chapter 5 Parameters|VFD-B Series

Over-Current Stall Prevention during Acceleration

06 - 01
Settings
A setting of 100% is equal to the Rated Output Current of the drive.
During acceleration, the AC drive output current may increase abruptly and exceed the value
specified by Pr.06-01 due to rapid acceleration or excessive load on the motor. When this
function is enabled, the AC drive will stop accelerating and keep the output frequency constant
until the current drops below the maximum value.
06-01
Over-Current
Detection
Level
06 - 02

Over-current Stall Prevention during Operation

Settings
If the output current exceeds the setting specified in Pr.06-02 when the drive is operating, the
drive will decrease its output frequency to prevent the motor stall. If the output current is lower
than the setting specified in Pr.06-02, the drive will accelerate again to catch up with the set
frequency command value.
5-66
20 to 250%
Over-Current Stall
prevention during
Acceleration,
frequency held
previous acceleration time
actual acceleration time when over-current stall
prevention is enabled
20 to 250%
Factory Setting: 170
output current
setting
frequency
Output
Frequency
Factory Setting: 170
Revision July 2008, BE16, SW V4.08 & V5.00
Unit: 1
time
Unit: 1