Delta VFD-B User Manual page 63

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

Chapter 5 Parameters|VFD-B Series
Parameter
Explanation
Source of Second
02-13
Frequency
Command
Source of Second
02-14
Operation Command
Keypad Frequency
02-15
Command
Group 3 Output Function Parameters
Parameter
Explanation
Multi-Function
03-00
Output Relay (RA1,
RB1, RC1)
Multi-Function
03-01
Output Terminal
MO1
Multi-Function
03-02
Output Terminal
MO2
Multi-Function
03-03
Output Terminal
MO3
5-6
Settings
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-11).
Last used frequency saved
05: RS-485 serial communication (RJ-11).
Last used frequency not saved.
06: Combined use of master and auxiliary
frequency command (See Pr. 02-10 to 02-
12)
00: Digital keypad (PU01)
01: External terminals. Keypad STOP/RESET
enabled.
02: External terminals. Keypad STOP/RESET
disabled.
03: RS-485 serial communication (RJ-11).
Keypad STOP/RESET enabled.
04: RS-485 serial communication (RJ-11).
Keypad STOP/RESET disabled.
0.00 ~ 400.00Hz
Settings
00: No function
01: AC drive operational
02: Master frequency attained
03: Zero speed
04: Over torque detection
05: Base-Block (B.B.) indication
06: Low-voltage indication
07: Operation mode indication
08: Fault indication
09: Desired frequency attained 1
10: PLC program running
11: PLC program step completed
12: PLC program completed
13: PLC program operation paused
14: Terminal count value attained
15: Preliminary count value attained
16: Auxiliary motor No.1
17: Auxiliary motor No.2
Factory
Revision July 2008, BE16, SW V4.08 & V5.00
Factory
Customer
Setting
00
00
60.00
Customer
Setting
08
01
02
20