Line Start Lockout - Delta VFD-B User Manual

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

02- 06

Line Start Lockout

Settings
This parameter determines the response of the drive when power is on and the operation
command source is changed.
Pr.02-06
Start lockout (Run when power is ON)
0
Disable (AC motor drive will run)
1
Enable (AC motor drive won't run)
2
Disable (AC motor drive will run)
3
Enable (AC motor drive won't run)
When the operation command source is from an external terminal and operation command is
ON (FWD/REV-DCM=close), the AC motor drive will operate according to Pr.02-06 after
power is applied. <For terminals FWD and REV only>
1.
When Pr.02-06 is set to 0 or 2, AC motor drive will run immediately.
2.
When Pr.02-06 is set to 1 or 3, AC motor drive will remain stopped until operation
command is received after previous operation command is cancelled.
Revision July 2008, BE16, SW V4.08 & V5.00
00
Disable. Operation status is not changed even if operation
command source Pr.02-01 and/or Pr.02-14 is changed.
01
Enable. Operation status is not changed even if operation command
source Pr.02-01 and/or Pr.02-14 is changed.
02
Disable. Operation status will change if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
03
Enable. Operation status will change if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
Chapter 5 Parameters|VFD-B Series
Factory Setting: 00
Operation status when operation
command source is changed
Keep previous status
Keep previous status
Change according to the new
operation command source
Change according to the new
operation command source
5-39