Delta VFD-B User Manual page 70

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

Parameter
Explanation
Under-Current
06-12
Detection Level
Under-Current
06-13
Detection Time
Under-Current
06-14
Detection Mode
Under-Current
06-15
Detection Restart
Delay Time (Lv)
User-Defined Low-
06-16
Voltage Detection
Level
User-Defined Low-
06-17
Voltage Detection
Time
06-18
Reserved
Group 7 Motor Parameters
Parameter
Explanation
07-00
Motor Rated Current 30 to 120%
Motor No-Load
07-01
Current
Torque
07-02
Compensation
07-03
Slip Compensation
(Used without PG)
07-04
Number of Motor
Poles
Motor Parameters
07-05
Auto Tuning
Motor Line-to-line
07-06
Resistance R1
07-07
Reserved
07-08
Motor Rated Slip
Slip
Compensation
07-09
Limit
07-10
Reserved
07-11
Reserved
Revision July 2008, BE16, SW V4.08 & V5.00
Settings
00~100% (00: Disabled)
0.1~ 3600.0 sec
00: Warn and keep operating
01: Warn and ramp to stop
02: Warn and coast to stop
03: Warn, after coast to stop, restart (delay
06-15 setting time)
1~600 Min.
00: Disabled
230V: 220 to 300VDC
460V: 440 to 600VDC
575V: 520 to 780VDC
0.1~ 3600.0 sec
Settings
01 to 90%
0.0 to 10.0
0.00 to 3.00
02 to 10
00: Disable
01: Auto tuning R1
02: Auto tuning R1 + no-load test
00~65535 mΩ
0.00 to 20.00 Hz
0 to 250%
Chapter 5 Parameters|VFD-B Series
Factory
Setting
00
10.0
00
10
00
0.5
Factory
Setting
100
40
0.0
0.00
04
00
00
3.00
200
Customer
Customer
5-13