Chapter 5 Parameters|VFD-B Series
Parameter
Explanation
Torque
07-12
Compensation Time
Constant
Slip Compensation
07-13
Time Constant
Accumulative Motor
07-14
Operation Time
(Min.)
Accumulative Motor
07-15
Operation Time
(Day)
Group 8 Special Parameters
Parameter
Explanation
DC Brake Current
08-00
Level
DC Brake Time
08-01
during Start-Up
DC Brake Time
08-02
during Stopping
Start-Point for DC
08-03
Brake
Momentary Power
08-04
Loss Operation
Selection
Maximum Allowable
08-05
Power Loss Time
B.B. Time for Speed
08-06
Search
Current Limit for
08-07
Speed Search
Skip Frequency 1
08-08
Upper Limit
Skip Frequency 1
08-09
Lower Limit
Skip Frequency 2
08-10
Upper Limit
Skip Frequency 2
08-11
Lower Limit
Skip Frequency 3
08-12
Upper Limit
Skip Frequency 3
08-13
Lower Limit
5-14
Settings
0.01 ~10.00 Sec
0.05 ~10.00 sec
00 to 1439 Min.
00 to 65535 Day
Settings
00 to 100%
0.0 to 60.0 sec
0.0 to 60.0 sec
0.00 to 400.00Hz
00: Operation stops after momentary power
loss
01: Operation continues after momentary
power loss, speed search starts with the
Master Frequency reference value
02: Operation continues after momentary
power loss, speed search starts with the
minimum frequency
0.1 to 5.0 sec
0.1 to 5.0 sec
30 to 200%
0.00 to 400.00 Hz
0.00 to 400.00 Hz
0.00 to 400.00 Hz
0.00 to 400.00 Hz
0.00 to 400.00 Hz
0.00 to 400.00 Hz
Revision July 2008, BE16, SW V4.08 & V5.00
Factory
Customer
Setting
0.05
0.10
00
00
Factory
Customer
Setting
00
0.0
0.0
0.00
00
2.0
0.5
150
0.00
0.00
0.00
0.00
0.00
0.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents