In Pr.06-08 to Pr.06-11 the four most recent faults that occurred, are stored. After removing the
cause of the fault, use the reset command to reset the drive.
06 - 12

Under-Current Detection Level

Settings
06 - 13

Under-Current Detection Time

Settings
06 - 14

Under-Current Detection Mode

Settings
Revision July 2008, BE16, SW V4.08 & V5.00
07
IGBT protection (occ)
08
CPU failure (cF3)
09
Hardware protection failure (HPF)
10
Current exceeds 2 times rated current during accel.(ocA)
11
Current exceeds 2 times rated current during decel.(ocd)
12
Current exceeds 2 times rated current during steady state operation
(ocn)
13
Ground fault (GFF)
14
Reserved
15
CPU READ failure (CF1)
16
CPU WRITE failure (CF2)
17
Reserved
18
Motor over load (oL2)
19
Auto accel/decel failure (CFA)
20
Software/password protection (codE)
21
Emergency stop (EF1)
22
Phase-Loss (PHL)
23
Preliminary count value attained, EF active (cEF)
24
Under-current (Lc)
25
Analog feedback signal error (AnLEr)
26
PG feedback signal error (PGErr)
00 ~ 100%
00 Disabled
0.1~ 3600.0 sec
00
Warn and keep operating
01
Warn and ramp to stop
02
Warn and coast to stop
03
Warn, after coast to stop, restart (delay 06-15 setting time)
Chapter 5 Parameters|VFD-B Series
Factory Setting: 00
Factory Setting: 10.0
Factory Setting: 00
Unit: 1
Unit: 0.1
5-69