B.5 Zero Phase Reactor (RF220X00A)
Dimensions are in millimeter and (inch)
Recommended Wire
Cable
Size
type
(Note)
2
AWG mm
≦10 ≦5.3
Single-
core
≦2 ≦33.6
≦12 ≦3.3
Three-
core
≦1 ≦42.4
Note: 600V Insulated unshielded Cable.
Note 1: The table above gives approximate
wire size for the zero phase reactors but the
selection is ultimately governed by the type
and diameter of cable fitted i.e. the cable
must fit through the center hole of zero
phase reactors.
Note 2: Only the phase conductors should
pass through, not the earth core or screen.
Note 3: When long motor output cables are
used an output zero phase reactor may be
required to reduce radiated emissions from
the cable
Call 1(800)985-6929 for Sales
deltaacdrives.com
VFD-VL
Wiring
Qty.
Method
Nominal
2
(mm
)
Diagram
1
≦5.5
A
Diagram
4
≦38
B
Diagram
1
≦3.5
A
Diagram
≦50
4
B
deltaacdrives.com
sales@deltaacdrives.com
Diagram A
Please wind each wire 4 times around the
core. The reactor must be put at inverter
output as close as possible.
Power
Supply
Diagram B
Please put all wires through 4 cores in
series without winding.
Power
R/L1
S/L2
Supply
T/L3
.
B-14
sales@deltaacdrives.com
Zero Phase Reactor
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
Zero Phase Reactor
U/T1
V/T2
W/T3
MOTOR
MOTOR