06 - 02
Over-current Stall Prevention during Operation
Settings
If the output current exceeds the setting specified in Pr.06-02 (the over-current stall
prevention current level during operation) when the drive is operating, the drive will
decrease its output frequency to prevent the motor stall. If the output current is lower
than the setting specified in Pr.06-02, the drive will then accelerate to catch up with the
frequency specified.
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Over-Current
Detection
Level
06-01
Over-Current Stall
prevention during
Acceleration,
frequency held
20 to 250%
Over-Current
Detection
Level
06-02
Over-Current Stall
Prevention during
Operation, output
frequency decrease
Current
Output Frequency
Output Current
Output
Frequency
5-39
VFD-B Series
Factory Setting: 170
Unit: 1%
5