Over-Current Stall Prevention During Operation; Over-Torque Detection Mode (Ol2); Over-Torque Detection Level - Delta VFD-EL-W Series User Manual

Sensorless vector control compact drive
Hide thumbs Also See for VFD-EL-W Series:
Table of Contents

Advertisement

Chapter 4 Parameters
VFD-EL-W
06.01
Over-Current
Detection
Level
Over-current Stall Prevention during Operation
06.02
Settings
If the output current exceeds the setting for Pr.06.02 when the drive is operating, the drive decreases its output
frequency to prevent motor stall. If the output current is lower than the setting for Pr.06.02, the drive
accelerates again to catch up with the set frequency command value.
06.03

Over-torque Detection Mode (OL2)

Settings
Determines the operation mode of the drive after detecting over-torque (OL2). It uses the following methods:
1.
If the output current exceeds the Over-torque Detection Level (Pr.06.04) and the detection time is
longer than the setting for Pr.06.05 (Over-torque Detection Time), the warning message "OL2"
displays.
2.
If a multi-functional output terminal is set to over-torque detection (Pr.03.00=4), the output is ON. Refer
to Pr.03.00 for details.
06.04
Over-torque Detection Level
Settings
10–200%
4-62
Over-Current Stall
prevention during
Acceleration,
frequency held
previous acceleration time
actual acceleration time when over-current stall
prevention is enabled
20–250%
0: Disable
Over-Current Stall
Prevention during
Over-Current
Operation, output
Detection
frequency decrease
Level
06.02

over-current stall prevention during operation

0
Over-torque detection disabled.
1
Over-torque detection enabled during constant speed operation. After over-
torque is detected, keep running until OL1 or OL occurs.
2
Over-torque detection enabled during constant speed operation. After over-
torque is detected, stop running.
3
Over-torque detection enabled during acceleration. After over-torque is
detected, keep running until OL1 occurs.
4
Over-torque detection enabled during acceleration. After over-torque is
detected, stop running.
output current
setting
frequency
Output
Frequency
time
Output Current
Output
Frequency
Unit: 1
Default: 170
Default: 0
Unit: 1
Default: 150