Adjusting The Analog Input - Omron SYSDRIVE 3G3JV Series User Manual

Compact simplified inverter
Hide thumbs Also See for SYSDRIVE 3G3JV Series:
Table of Contents

Advertisement

Basic Operation

5-5-3 Adjusting the Analog Input

Input characteristic adjustments may be necessary for analog frequency
references to be input. At that time, use the following parameters for gain,
bias, and filter time parameter adjustments.
FR Terminal Adjustments for Frequency Reference Input
Gain and Bias Settings (n41 and n42)
Set the input characteristics of analog frequency references in n41 (for the frequency
reference gain) and n42 (for the frequency reference bias).
Set the frequency of maximum analog input (10 V or 20 mA) in n41 as percentage
based on the maximum frequency as 100%.
Set the frequency of minimum analog input (0 V, 0 mA, or 4 mA) in n42 as percentage
based on the maximum frequency as 100%.
Frequency Reference Gain
n41
Setting
0% to 255%
range
(Max. frequency = 100%)
Frequency Reference Bias
n42
Setting
–99% to 99%
range
(Max. frequency = 100%)
Filter Time Constant Settings (n43)
The digital filter with a first-order lag can be set for analog frequency references to be
input.
This setting is ideal if the analog input signal changes rapidly or the signal is subject to
noise interference.
The larger the set value is, the slower the response speed will be.
n43
Analog Frequency Reference Filter Time
Setting
0.00 to 2.00 (s)
range
5-10
Unit of
1%
setting
Unit of
1%
setting
Unit of
0.01 s
setting
Chapter 5
Changes during
operation
Default setting
Changes during
operation
Default setting
Changes during
No
operation
Default setting
0.10
Yes
100
Yes
0