Advertisement

5 Basic Settings

5-10-3 Multi-function Output ON/OFF Delay Time

• Each multi-function output terminal can be allocated with the ON/OFF delay time independently.
• Because all output signals turn ON/OFF immediately when the set conditions are met, depending on
the selected signal, chattering may occur. In such a case, use this function to hold or delay the signal.
• Set the parameter independently for each output terminal.
For the output terminal, multi-function output terminals P1 and P2 and a multi-function relay output
MA, MB
terminal are provided.
(
)
The correspondence between each output terminal and the related ON/OFF delay parameter is
shown in the table below.
Parameter
No.
C130
Multi-function Output P1 ON Delay Time
C132
Multi-function Output P2 ON Delay Time
C140
Multi-function Relay Output ON Delay
C131
Multi-function Output P1 OFF Delay Time
C133
Multi-function Output P2 OFF Delay Time
C141
Multi-function Relay Output OFF Delay

5-10-4 Signal during RUN (RUN)

• The RUN signal is output during inverter operation.
• Allocate one of the Multi-function Output P1 Selection or Multi-function Output P2 Selection
(C021/C022), or Multi-function Relay Output (MA, MB) Function Selection (C026), to 00 (RUN).
• The RUN signal is also output when the inverter is decelerating after the RUN command turns OFF
or DC injection braking is active.
• The RUN signal will not be output even if the RUN command is input when the frequency reference is
0 Hz and the output reference reaches 0 Hz.
(Note that on the Digital Operator, the RUN LED is lit when the RUN command is ON.)
Parameter
No.
C021, C022
Multi-function Output P1/P2 Selection
Multi-function Relay Output (MA, MB)
C026
Function Selection
The timing diagram is as follows.
The inverter outputs the RUN (during RUN) signal until the motor is stopped even if the RUN command
(FW) turns OFF.
Output
frequency
FW
RUN
5 - 56
Function name
Function name
ON
OFF
ON
OFF
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Default
Data
0.0 to 100.0
0.0 to 100.0
Default
Data
00:
RUN (Signal dur-
ing RUN)
Unit
data
0.0
s
0.0
s
Unit
data
05