3 Operation and Test Run
3-1-2

Key Operation Method

This section explains how to use the Digital Operator keys in a typical operation (when the Display
Selectionis "Complete display") and in the extended function mode U as operation examples.
This operation will be the same even if you select a setting other than Complete display in the Display
Selection (b037), although the number of parameters that you will see on the display differs.
Precautions for Correct Use
• You can change the parameter display on the Digital Operator by the Display Selection
(b037). For details, refer to 5-1-1 Display Selection on page 5-3.
• In the 3G3MX2-V1 Series, the default data for the Display Selection (b037) was changed
from the previous default 04 (Basic display) to 00 (Complete display). You can see and set all
parameters when you turn on the power supply for the first time.
Additional Information
• You can set the initial screen displayed after turning on the power supply by the Initial Screen
Selection (b038). For details, refer to 7-6-5 Initial Screen Selection (Initial Screen after
Power-on) on page 7-56.
• You can display only the parameters registered as user parameters. It is also possible to
automatically register changed parameters, or directly set specific parameters. For details,
refer to 7-6-11 User Parameter Automatic Setting Function on page 7-60.
Item
Display Selection
Initial Screen Selec-
tion (Initial screen
after power-on)
User Parameter
Automatic Setting
Function
Additional Information
Regardless of the display mode of the Digital Operator, if you press the Mode key for 3 seconds
or more, the data of Output Frequency Monitor (d001) is displayed. However, the Digital
Operator continues to display the function group parameters in sequence as the normal
operation if you press the Mode key for less than 3 seconds. (Example: F001 → A001 → b001
→ C001 ··· after 3 seconds, "0.00 (data of Output Frequency Monitor)" appears)
3 - 6
Parameter No.
Data
b037
00
01
02
03
04
05
b038
000
001 to 060
201
202
b039
00
01
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Description
Complete display (Factory default)
Individual display of functions
User setting + d001, F001, b037
Data comparison display
Basic display
Monitor display + b037
Screen on which the Enter key was last pressed
d001 to d060 (001: Factory default)
F001
Do not set.
Disabled (Factory default)
Enabled