Feedback Selection

Select the terminals used to input the feedback signal in PID Feedback Selection (A076).
When the 1st Frequency Reference Selection (A001) is set to 01 (Control circuit terminal block), the
analog input setting other than that selected in A076 is used as the target frequency reference. In this
case, the setting in A005 and the function allocated to the terminal AT (Analog input switching) are dis-
abled.
When the PID Feedback Selection (A076) is set to 02 (Modbus communication), write the feedback
value (100% = 10000) to the holding register address 0006 hex.
Register
No.
0006 hex
PID Feedback Selection
Note Although this register supports read and write operations, you can write data only when the PID Feedback
Selection (A076) is set to 02 (Modbus communication). You cannot write data with other settings.
When the PID Feedback Selection (A076) is set to 03 (Pulse train input), the inverter recognizes the
captured pulse train frequency value [Hz] relative to the pulse train frequency set in the Pulse Train Fre-
quency Scale (P055) as the maximum frequency. As a result, for the feedback value, the inverter cap-
tures a value converted into a percentage as 100% of the maximum frequency.
For the pulse train input frequency, refer to 7-5-16 Pulse Train Frequency Input on page 7-52.
Feedforward Selection
Select the terminals used to input the feedback signal in the PID Feedback Selection (A079).
In A079, you can set a target value, or have a setting that overlaps with the PID Feedback Selection
value.
With an overlapping setting, the analog input is used for both the feedback and feedforward signals.
If A079 is set to Disabled, feedforward control will not be performed.
PID Deviation Reverse Output
Depending on the sensor characteristics, etc., the polarity of deviation between the target and feedback
values may not match the inverter's command. In this case, you can invert the deviation polarity by set-
ting the PID Deviation Reverse Output (A077) to 01.
(Example) To control a refrigerator compressor
If you are using a temperature sensor designed for use in a temperature range of 0 to
100°C at 0 to 10 V and the target and current temperatures are 5°C and 10°C, respectively,
the inverter attempts to reduce the frequency under PID control since the feedback value is
larger than the target value.
In this case, set A077 to 01. Then, the inverter attempts to increase the frequency.
PID target value
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Parameter
Function name
No.
(00)
-1
(01)
PID feedback value
R/W
Monitor or setting data
R/W
0 to 10000
A077
PID
operation
7 Other Functions