Omron MX2 Series User Manual page 150

Mx2 series type v1 multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

4 Parameter List
Parameter
Function name
No.
1st Overload Limit
b021
Selection
2nd Overload Limit
b221
Selection
1st Overload Limit
b022
Level
2nd Overload Limit
b222
Level
1st Overload Limit
b023
Parameter
2nd Overload Limit
b223
Parameter
1st Overload Limit
b024
Selection 2
1st Overload Limit
b025
Level 2
1st Overload Limit
b026
Parameter 2
Overcurrent Sup-
b027
pression Selection
Frequency Pull-in
b028
Restart Level
Frequency Pull-in
b029
Restart Parameter
Starting Frequency
Selection at
b030
Frequency Pull-in
Restart
*1. The default data was changed from the previous model.
4 - 16
Monitor or data range
00: Disabled
01: Enabled during acceleration
and constant speed
02: Enabled during constant
speed
03: Enabled during acceleration
and constant speed (Accel-
erated during regeneration)
0.20 × Rated current to 2.00 ×
Rated current (Heavy load)
0.20 × Rated current to 1.50 ×
Rated current (Light load)
0.1 to 999.9
1000. to 3000.
00: Disabled
01: Enabled during acceleration
and constant speed
02: Enabled during constant
speed
03: Enabled during acceleration
and constant speed (Accel-
erated during regeneration)
0.20 × Rated current to 2.00 ×
Rated current (Heavy load)
0.20 × Rated current to 1.50 ×
Rated current (Light load)
0.1 to 999.9
1000. to 3000.
00: Disabled
01: Enabled
02: Enabled (at reduced voltage
startup)
0.20 × Rated current to 2.00 ×
Rated current (Heavy load)
0.20 × Rated current to 1.50 ×
Rated current (Light load)
0.1 to 999.9
1000. to 3000.
00: Frequency at interruption
01: Maximum frequency
02: Set frequency (Frequency
reference)
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Setting
Default
Set
during
data
data
RUN
01
Disabled
01
Disabled
Rated
Disabled
current
×
1.50
(Heavy)
Disabled
1.20
(Light)
1.0
Disabled
1.0
Disabled
01
Disabled
Rated
current
×
1.50
Disabled
(Heavy)
1.20
(Light)
1.0
Disabled
*1
Disabled
01
Rated cur-
rent of
Disabled
inverter
0.5
Disabled
00
Disabled
Changes
during
Unit
Page
RUN
Enabled
Enabled
Enabled
A
Enabled
A
Enabled
s
Enabled
P. 7-76
Enabled
Enabled
A
Enabled
s
Enabled
P. 7-79
Enabled
A
P. 5-45
Enabled
s
P. 7-61
Enabled

Hide quick links: