Wiring method

With DC reactor
3-phase 200 VAC
Single-phase 200 VAC
3-phase 400 VAC
*1. Connect to the terminals L1 and N on the single-phase 200-VAC inverter.
With DC reactor and AC reactor
Power
supply
3-phase 200 VAC
Single-phase 200 VAC
3-phase 400 VAC
*1. Connect to the terminals L1 and N on the single-phase 200-VAC inverter.
Effect of reactors
Through the use of the DC/AC reactor, the rate of harmonic current occurrences can be reduced as
shown in the table of typical examples below (excerpt from a JEMA document).
Measure against
harmonics
None (Inverter only)
With AC reactor
With DC reactor
With DC and AC reactors
Guideline for reactor selection
When implementing measures against harmonics, first install a DC reactor and evaluate its effect.
Then, if further reduction is required, add an AC reactor.
To implement harmonic countermeasures in consideration of the power supply environment (such
as rapid change in the power supply voltage), first install an AC reactor and evaluate its effect. Then,
if further reduction is required, add a DC reactor.
If you have multiple inverters and use the AC reactor, use one AC reactor for each inverter. Using
only one AC reactor for more than one inverter does not provide sufficient reduction.
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Power
MCCB
MC
supply
*1
MCCB
MC
AC reactor
*1
(optional)
5th
7th
65
41
38
14.5
30
13
28
9.1
DC reactor
(optional)
+1
P/+2
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
DC reactor
(optional)
+1
P/+2
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
Harmonic current occurrence rate [%]
11th
13th
17th
8.5
7.7
4.3
7.4
3.4
3.2
8.4
5
4.7
7.2
4.1
3.2
2 Design
M
M
19th
23rd
25th
3.1
2.6
1.8
1.9
1.7
1.3
3.2
3.0
2.2
2.4
1.6
1.4
2 - 27