7 Other Functions
7-1
Monitor Mode
This section describes the output frequency, fault monitor during trip, and other monitor functions of the
inverter.
7-1-1
Output Frequency Monitor [d001]
Use this function to display the output frequency of the inverter. The value is 0.00 when the inverter is
stopped.
The monitor display LED "Hz" is lit while the value of d001 is displayed.
Parameter
No.
Output Frequency
d001
Monitor
d001/d007 Data Set-
b163
ting Selection
Related functions
Additional Information
• When the 1st/2nd Frequency Reference Selection (A001/A201) is set to 02 (Digital Operator:
F001), if the d001/d007 Data Setting Selection (b163) is set to 01 (Enabled), you can change
the Output Frequency Monitor (d001) by the Increment/Decrement key only during operation.
• The Output Frequency Monitor (d001) value is reflected on the Output Frequency Set-
ting/Monitor (F001) setting and stored to the EEPROM when you press the Enter key.
• Because the inverter updates the F001 value while displaying d001, the input value may not
be displayed immediately depending on the acceleration/deceleration time.
• The monitor value cannot be changed while the PID function is activated/stopped.
• In the individual input mode, it is not possible to change the frequency by simultaneously
pressing the Increment and Decrement keys.
7-1-2
Output Current Monitor [d002]
Use this function to display the output current value of the inverter. The value is 0.0 when the inverter is
stopped.
The monitor display LED "A" is lit while the value of d002 is displayed.
Parameter
No.
d002
Output Current Monitor
7 - 4
Function name
0.00 to 99.99 (Displayed in increments of 0.01)
100.0 to 400.0 (Displayed in increments of 0.1)
00:
Disabled
(Frequency cannot be changed in
d001/d007)
01:
Enabled
(Frequency can be changed in
d001/d007)
A001, A201, F001, d007
Function name
0.0 to 655.3
Minimal unit depends on inverter capacity.
Data
Data
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Default
Unit
data
−
Hz
−
00
Default
Unit
data
−
A