Other Operation Functions; Starting Frequency - Omron MX2 Series User Manual

Mx2 series type v1 multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

7-5

Other Operation Functions

This section describes the parameters associated with other operation functions.
7-5-1

Starting Frequency

Set the frequency at which the inverter starts its output when the RUN signal turns ON.
Mainly, use this function to adjust the starting torque.
If you set a high frequency in Starting Frequency (b082), the inverter starts with the full voltage and also
the starting current increases. Therefore, the overload limit function may be performed or the inverter
may trip easily by the overcurrent protection.
Parameter No.
b082
*1. The default data was changed from the previous model.
RUN command
(FW input)
Output frequency
Output voltage
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Function name
Starting Frequency
0.01 to 9.99
b082
7 Other Functions
Default
Data
Unit
data
*1
Hz
1.50
7
7 - 35