Omron MX2 Series User Manual page 403

Mx2 series type v1 multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

• When the DC Injection Braking Delay Time (A053) is set, the inverter shuts off its output and remains
in a free-run sate during the set time. After the expiration of the set time, the inverter starts DC injec-
tion braking.
• In the DC Injection Braking Edge/Level Selection (A056), you can set the operation of DC injection
braking after the terminal DB turns ON.
Select optimal operation according to your system, with reference to the example below.
• When A056 is set to 00 (Edge operation), you need to also set the time during which DC injection
braking is applied in the DC Injection Braking Time (A055).
(a) Edge operation (A056 = 00)
(Example 1-a)
FW input
DB input
Output
frequency
*1. Set the DC Injection Braking Time (A055) or the DC injection time by DB input in consideration of the heat
generation of the motor.
(a) Edge operation (A056 = 00)
(Example 2-a)
FW input
DB input
Output
frequency
(Example 3-a)
FW input
DB input
Output
frequency
Note During free running and during DB operation, the output frequency is 0.
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
(Example 1-b)
*1
A055
(Example 2-b)
A055
(Example 3-b)
Free running
A055
A053
(b) Level operation (A056 = 01)
FW input
DB input
Output
frequency
(b) Level operation (A056 = 01)
FW input
DB input
Output
frequency
FW input
DB input
Output
frequency
A053
7 Other Functions
*1
Free running
7 - 93