7 Other Functions
7-8-20 Window Comparator (WCFV/WCFI) (Disconnection Detection
FVDc/FIDc)
The window comparator signal will be output when the analog input FV/FI value is between the upper
and lower limit settings. It is useful for monitoring the analog input at a level to detect disconnection or
other faults.
The hysteresis width can be set for the upper and lower limit level settings for the window comparator
function.
In addition to the hysteresis width, the upper and lower limit levels can be set individually for each of the
analog input signals FV and FI.
The analog operation level during WCFV/WCFI output can be set to a fixed value. To do so, set the
Analog Operation Level at FV/FI/FE Disconnection (b070/b071). When set to no, the analog input value
will be used "as is."
The signals FVDc and FIDc will be output in the same way as WCFV and WCFI, respectively.
Parameter
No.
Window Comparator FV
b060
Upper Limit Level
Window Comparator FI Upper
b063
Limit Level
Window Comparator FV
b061
Lower Limit Level
Window Comparator FI Lower
b064
Limit Level
Window Comparator FV Hys-
b062
teresis Width
Window Comparator FI Hys-
b065
teresis Width
Analog Operation Level at FV
b070
Disconnection
Analog Operation Level at FI
b071
Disconnection
Multi-function Output P1/P2
C021
Selection
C022
Multi-function Relay Output
C026
(MA, MB) Function Selection
Note Set the upper and lower limit level settings for the window comparator function as a percentage [%] of the
input voltage (10 V) or current (20 mA).
7 - 88
Function name
Lower limit level + Hysteresis width × 2
(0. min.) to 100.
Set an upper limit level.
0. to Lower limit level − Hysteresis width ×
2 (100. max.)
Set a lower limit level.
0. to (Upper limit level − Lower limit level)
÷ 2 (10. max.)
Set a hysteresis width for the upper and
lower limit levels.
0. to 100.
255: no (Disabled)
Set the analog operation level during
WCFV/WCFI (FVDc/FIDc) output.
27:
28:
54:
55:
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Data range
FVDc (Analog FV disconnection
detection)
FIDc (Analog FI disconnection
detection)
WCFV
(Window Comparator FV)
WCFI
(Window Comparator FI)
Default
Unit
data
100.
%
0.
%
0.
%
no