12-15Devicenet Communications Unit (Model: 3G3Ax-Mx2-Drt-E); Specifications - Omron MX2 Series User Manual

Mx2 series type v1 multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

12 Options
12-15DeviceNet Communications Unit
(Model: 3G3AX-MX2-DRT-E)

12-15-1 Specifications

Mounting
Environment
DeviceNet
interface
DeviceNet
configuration
12 - 48
Item
Unit type
Model
Weight
Operating ambient
temperature
Operating ambient
humidity
Storage ambient
temperature
Vibration resistance
Dielectric strength
Location
Compliance with EMC and
electrical safety standards
UL/cUL standard
Enclosure rating
Communications protocol
Certification
DeviceNet profile
Supported connections
Communications power
supply
Unit device address range Node address MAC ID 0 to 63, set via inverter parameter P192 or
Supported baud rates
Default connection path
Supported assemblies
EDS file
Specifications
MX2 Series DeviceNet Communications Unit
3G3AX-MX2-DRT-E
100 g max. (Shipping weight: Approx. 170 g)
−10 to 50°C (with no freezing or condensation)
20% to 90%
−20 to 65°C (with no freezing or condensation)
2
5.9 m/s
(0.6 G), 10 to 55 Hz
500 VAC (between isolated circuits)
At a maximum altitude of 1,000 m, indoors (without corrosive
gases or dust)
EN61800-3: 2004 (2004/108/EC) Second environment, Category C3
EN61800-5-1: 2007(2006/95/EC) SELV
UL508
IP20
DeviceNet
DeviceNet conformance test
AC drive (0×02)
Remote I/O: Master-Slave connection
Poll
Explicit message
Conforming to the DeviceNet specifications
11 to 25 VDC (50 mA max., typ. 20 mA)
rotary switch
125, 250, or 500 kbps
Automatic baud rate detection by Master Unit
Supported, set via inverter parameter P046
Basic Speed I/O (Output assembly 20, Input assembly 70)
Extended Speed I/O (21, 71)
Extended Speed and Torque Control (123, 173)
Special I/O (100, 150)
Extended Control I/O (101, 151)
Extended Control I/O and Multi-function Input Monitor (101, 153)
Flexible format (139, 159)
Extended Speed and Acceleration Control (110, 111)
In case the DeviceNet Master Unit is configured using user
allocation, only the input/output pairs can be configured.
Dependent on inverter model
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents