Low-voltage directive
The 3G3MX2-V1 Series Inverter complies with EN61800-5-1 when installed and wired to equipment
according to the methods described below.
• The 3G3MX2-V1 Series Inverter is an open type device. Be sure to install it inside the control panel.
• The power supply and voltage (SELV) with reinforced or double insulation should be used for wiring
to the control circuit terminals.
• To satisfy requirements of the LVD (Low Voltage Directive), the inverter must be protected with fuses
or a molded case circuit breaker (MCCB) in case a short-circuiting accident occurs. Be sure to install
fuses or a molded case circuit breaker (MCCB) on the power supply side of the inverter.
The fuses, if used, should be one of the UL-compliant Class-J product listed in A-4 UL/cUL Standards
Cautions on page A-10.
• Use one molded case circuit breaker (MCCB), or one set of fuses, per inverter.
• Use the crimp terminal with an insulation sleeve to connect to the main circuit terminals.
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
2 Design
2
2 - 47