5 Basic Settings
Binary Operation
• Setting the Multi-function Input S1 to S7 Selection (C001 to C007) to 02 (CF1) to 05 (CF4) enables
the selection of the multi-step speed 0 to 15.
• Use the Multi-step Speed Reference 1 to 15 (A021 to A035) to set the frequency for the multi-step
speed 1 to 15.
• Use the 1st/2nd Frequency Reference Selection (A001/A201) to set the 1st/2nd Multi-step Speed
Reference 0 (A020/A220).
Set the 1st/2nd Frequency Reference Selection (A001/A201) to 02 (Digital Operator: F001) to enable
the 1st/2nd Multi-step Speed Reference 0 (A020/A220).
If A001/A201 are set to 01 (Control circuit terminal block: Analog input), the analog input is used as
the frequency reference to set the 1st/2nd Multi-step Speed Reference 0.
Parameter
No.
C001 to
Multi-function Input S1 to
C007
S7 Selection
Multi-step Speed/Position
C169
Determination Time
Multi-step
CF4
speed
0th
1st
2nd
3rd
OFF
4th
5th
6th
7th
8th
9th
10th
11th
ON
12th
13th
14th
15th
• For multi-step speed binary operation, the wait time until the inverter recognizes terminal input can be
set in the Multi-step Speed/Position Determination Time (C169). This prevents the transitional status
before terminal input is recognized from being accepted.
• Input data will be determined if it remains unchanged for the time set in the Multi-step Speed/Position
Determination Time (C169). Note that setting a long determination time results in a slow input
response.
With zero determination time
(C169)
Frequency reference
CF1
CF2
CF3
CF4
5 - 50
Function name
02: CF1 (Multi-step speed setting binary 1)
03: CF2 (Multi-step speed setting binary 2)
04: CF3 (Multi-step speed setting binary 3)
05: CF4 (Multi-step speed setting binary 4)
0. to 200. (× 10 ms)
CF3
CF2
CF1
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
15
11
9
Determination time
1
(C169)
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Data
10th
9th
4th
5th
3rd
6th
2nd
7th
1st
8th
CF1
CF2
CF3
CF4
FW
With determination time
13
5
4
Default data
Unit
0.
ms
11th
Frequency from
Digital Opera-
12th
tor or external
13th
analog input
terminal
14th
15th
0th
(C169)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents