5 Basic Settings
5-4

RUN Command Settings

5-4-1

RUN Command Selection

Select the input method for the RUN command.
Parameter
No.
A002/A202
F004
Related functions
Below are the details of the parameter settings.
Data
01
02
03
04
• If you select 01 (Control circuit terminal block) in the RUN Command Selection, set any two of the
Multi-function Input S1 to S7 Selection (C001 to C007) to 00 (FW: Forward) and 01 (RV: Reverse).
• Also, when using the 3-wire input function, set the RUN Command Selection to 01 (Control circuit ter-
minal block).
For details on the 3-wire input function, refer to 5-9-9 3-wire Input Function (STA, STP, F/R) on page
5-54.
• When the Multi-function Input S1 to S7 Selection is set to 31 (OPE: Forced operator function) or 51
(F-TM: Forced terminal block), the setting has priority over the 1st/2nd Frequency Reference Selec-
tion (A001/A201) and 1st/2nd RUN Command Selection (A002/A202).
When each terminal is input, the frequency reference and RUN command from the Digital Operator
or the control terminal block are enabled.
• When using the DriveProgramming function to input the RUN command, set the RUN Command
Selection to 01 (Control circuit terminal block).
For details, refer to "DriveProgramming User's Manual (I580)".
• To use the Digital Operator to input the RUN command, set the RUN direction in the RUN Direction
Selection (F004).
5 - 22
Function name
01:
Control circuit terminal block
(DriveProgramming)
1st/2nd RUN Com-
02:
Digital Operator
mand Selection
03:
Modbus communication
04:
Option
00:
Forward
RUN Direction
Selection
01:
Reverse
F004, C001 to C007
Inputs the RUN command via the ON/OFF of the FW/RV signal allocated to the control circuit
terminal block.
It will be regarded as the STOP command if both the forward and reverse commands are input
simultaneously.
Inputs the RUN command via the RUN key and the STOP/RESET key on the Digital Operator.
Inputs the RUN command via Modbus communication.
Inputs the RUN command via the mounted communications option unit.
Data
RUN command source
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Default data
Unit
02
00