7-5-4

Acceleration/Deceleration Stop Function

This function causes the inverter stop accelerating/decelerating temporarily and start running at a con-
stant speed at the frequency output at that time.
If the moment of inertia of a load machine is large, you can use it, for example, to have the motor wait
until the amount of motor slip during acceleration/deceleration becomes small. You can use it also to
prevent an overcurrent/overvoltage trip during acceleration/deceleration.
This function works independently of the Acceleration/Deceleration Pattern Selection (A097/A098) set-
ting. It is activated for all acceleration/deceleration patterns by the frequency reference input via the
analog input signal or the optional Digital Operator's volume control (VR).
There are two acceleration/deceleration stop methods as follows, which can be used in conjunction
with each other.
• Stopping automatically when the specified frequency/stop time is reached
• Stopping by inputting the terminal HLD (83: Retain output frequency) set in the Multi-function Input
S1 to S7 Selection (C001 to C007)
Using this function prolongs the acceleration/deceleration time configured by the F001/F202 and
F003/F203 settings for the duration of the stop time caused by this function.
Parameter
No.
Acceleration Stop
A069
Frequency
A070
Acceleration Stop Time
Deceleration Stop
A154
Frequency
A155
Deceleration Stop Time
Multi-function Input S1 to
C001 to C007
S7 Selection
Stopping when the specified frequency/stop time is reached
Output frequency
A154
A069
Stopping via input to a multi-function input terminal
Output frequency
HLD input
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
Function name
0.00 to Starting Frequency: Disabled
Frequency above Starting Frequency to 400.0
0.0:
0.1 to 60.0
0.00 to Starting Frequency: Disabled
Frequency above Starting Frequency to 400.0
0.0:
0.1 to 60.0
83:
A155
A070
Time
Time
Data
Disabled
Disabled
HLD (Retain output frequency)
7 Other Functions
Default
Unit
data
0.00
Hz
0.0
s
0.00
Hz
0.0
s
7 - 37
7