H Setting Control Input Responsiveness (b1-06)
Parameter b1-06 is used to set the responsiveness of the control inputs (forward/reverse and multi-
function inputs); it cannot be changed during operation.
Parameter
Display name
p y
number
b1-06
Cntl Input Scans
Settings
Setting
Name
0
2mS – 2 Scans
1
5mS – 2 Scans
Note Set the responsiveness to match the type of control inputs being used. Use a setting of "1" if there
is even one contact input.

5-1-5 Acceleration/Deceleration Time Settings

H Acceleration/Deceleration Time Units (C1-10)
Parameter C1-10 is used to set the units for the acceleration and deceleration time settings in C1-01
through C1-08. Setting C1-10 to "0" allows the acceleration and deceleration times to be set very pre-
cisely, but reduces the maximum time setting from 6000.0 s to 600.00 s.
This parameter cannot be changed during operation.
Parameter
Display name
p y
number
C1-10
Acc/Dec Units
Settings
Setting
Name
0
0.01 Seconds
1
0.1 Seconds
H Acceleration/Deceleration Time Settings (C1-01 through C1-08)
Parameters C1-01 through C1-08 set the acceleration and deceleration times individually.
Digital Operator
Control circuit terminals (external terminals)
Not used. (Do not set.)
Optional Card (CompoBus/D Communications Card or SYSMAC BUS I/F
Card)
Not used. (Do not set.)
Setting
g
Units
Default
range
setting
0 or 1
---
1
Two scans every 2 ms (Use when connecting transistor outputs.)
Two scans every 5 ms (Use when connecting contact outputs or switches.)
Setting
g
Units
Default
range
setting
0 or 1
---
1
Sets the acceleration/deceleration time units to 0.01 seconds.
Sets the acceleration/deceleration time units to 0.1 seconds.
Run source
Valid access levels
V/f
V/f with
Open Loop
Control
PG
Advanced
Function
Valid access levels
V/f
V/f with
Open Loop
Control
PG
Advanced
Function
Chapter 5
Flux
Vector
Vector
Flux
Vector
Vector
5-11