Basic Operation

Key sequence
Select Language
English
Access Level
Quick Start
A1-01=
Quick-Start
A1-01=
2 times
Advanced
Entry Accepted
Access Level
Advanced Level
H Setting the Control Mode (A1-02)
Parameter A1-02 is used to select one of the four control modes. This parameter is not initialized by the
initialize operation and it cannot be changed during operation.
Parameter
Display name
p y
number
A1-02
Control Method
Control Mode Settings
Setting
Name
0
V/f Control
1
V/f w/PG Fdbk
2
Open Loop Vector Vector control without pulse generator
3
Flux Vector
Display
2 ***
4
Setting
g
Units
range
0 to 3
---
2
V/f control without pulse generator (normal V/f control)
V/f control with pulse generator (V/f control using a PG Speed Control Card)
(Vector control using the Inverter's internal speed information)
Vector control with pulse generator
(Vector control using a PG Speed Control Card)
Explanation
Puts the Unit in initialize mode.
(Select Language display)
Displays the Access Level (A1-01).
Displays the parameter setting for A1-01.
Changes the setting to Advanced.
Writes the new setting.
Returns to the Access Level display.
Valid access levels
Default
setting
V/f
V/f with
Control
Quick-start, Basic, or Advanced
Function
Chapter 5
Open Loop
PG
Vector
Flux
Vector
5-3