Installation
H Wiring on the Input Side of the Main Circuit
Installing a Molded-case Circuit Breaker
Always connect the power input terminals (R/L1, S/L2, and T/L3) and power supply via a molded case
circuit breaker (MCCB) suitable to the Inverter.
Install one wiring circuit breaker per Inverter.
Choose an MCCB with a capacity of 1.5 to 2 times the Inverter's rated current.
For the MCCB's time characteristics, be sure to consider the Inverter's overload protection (one min-
ute at 150% of the rated output current).
If the MCCB is to be used in common among multiple Inverters, or other devices, set up a sequence
such that the power supply will be turned OFF by a fault output, as shown in the following diagram.
Power
supply
3-phase/
Single-phase
200 V AC
3-phase
400 V AC
Note Use a 400/200 V transformer for a 400-V model.
Installing a Ground Fault Interrupter
Inverter outputs use high-speed switching, so high-frequency leakage current is generated.
In general, a leakage current of approximately 100 mA will occur for each Inverter (when the power
cable is 1 m) and approximately 5 mA for each additional meter of power cable.
Therefore, at the power supply input area, use a special-purpose breaker for Inverters, which detects
only the leakage current in the frequency range that is hazardous to humans and excludes high-fre-
quency leakage current.
For the special-purpose breaker for Inverters, choose a ground fault interrupter with a sensitivity
amperage of at least 10 mA per Inverter.
When using a general leakage breaker, choose a ground fault interrupter with a sensitivity amperage
of 200 mA or more per Inverter and with an operating time of 0.1 s or more.
2-28
(See note.)
Chapter 2
Inverter
19
Fault output (NC)
20