Installation
I/O Circuit Configuration
PG power
supply +12 V
A-phase
pulse input
B-phase
pulse input
Note When connecting to a voltage-output-type PG (encoder), select a PG that has an output imped-
ance with a current of at least 12 mA to the input circuit photocoupler (diode). The E6B2-CWZ3E
cannot be used.
3G3FV-PPGD2 (For V/f With PG Feedback Mode Only)
Three-phase
200 VAC (400 VAC)
Note 1. Twisted-pair shielded wire must be used for signal lines.
Note 2. Do not use the pulse generator's power supply for anything other than the pulse generator
(encoder). Using it for another purpose can cause malfunctions due to noise.
Note 3. The length of the pulse generator's wiring must not be more than 50 meters.
+12 V
Division rate circuit
0 V
A-phase
pulses
B-phase
pulses
L1
T1
L2
T2
L3
T3
Forward output pulses
3G3FV-PPGD2
Power supply 0 V
Power supply 5 V
Pulse output + (A/B phase)
Pulse output –
(A/B phase)
Pulse monitor output
Chapter 2
A-phase pulse
monitor output
B-phase pulse
monitor output
A-phase pulses
B-phase pulses
Encoder
2-45