Omron SYSDRIVE 3G3FV User Manual page 99

High-function general-purpose inverter
Table of Contents

Advertisement

Preparing for Operation
Access Level Settings
Setting
Name
0
Operation Only This setting allows operation mode and initialize mode to be displayed or
1
User Level
2
Quick-start
3
Basic
4
Advanced
S Setting the Control Mode
Use parameter A1-02 to select one of the four control modes. This parameter is not initialized by the
initialize operation and it cannot be changed during operation.
Parameter
Display name
p y
number
A1-02
Control Method
Control Mode Settings
Setting
Name
0
V/f Control
1
V/f w/PG Fdbk
2
Open Loop Vector Vector control without pulse generator
3
Flux Vector
Control Mode Characteristics
Characteristic
Basic control method
Speed detector
Optional Speed
Detectors
Speed control range
Starting torque
Speed control
precision
Torque limit
Torque control
Example applications
changed. Use this setting to prevent parameter settings from being changed.
This setting allows only the user-selected parameters (up to 32) to be displayed
or changed. Select the desired parameters as "User Parameters" in parameters
A2-01 through A2-32.
This setting allows the parameters required to start the Inverter (about 25) to be
displayed or changed.
This setting allows the commonly used parameters to be displayed or changed.
This setting allows all parameters to be displayed or changed.
Setting
g
Units
range
0 to 3
---
V/f control without pulse generator (normal V/f control)
V/f control with pulse generator (V/f control using a PG Speed Control Card)
(Vector control using the Inverter's internal speed information)
Vector control with pulse generator
(Vector control using a PG Speed Control Card)
V/f Control
Voltage/frequency
Voltage/frequency
control (open loop)
control with speed
compensation
Not required
Required
(pulse generator)
Not required
3G3FV-PPGA2 or
3G3FV-PPGD2
1:40
1:40
150%/3 Hz
150%/3 Hz
2 to 3%
0.03%
Not possible
Not possible
Not possible
Not possible
Multiple motors
Simple speed
feedback control
Function
Default
setting
V/f
Control
2
Quick-start, Basic, or Advanced
Function
V/f w/PG Fdbk
Open Loop Vector
Current vector con-
trol without PG
Not required
Not required
1:100
150%/1 Hz
0.2%
Possible
Not possible
Variable speed
drive applications
Chapter 3
Valid access levels
V/f with
Open Loop
PG
Vector
Flux Vector
Current vector con-
trol with PG
Required
(pulse generator)
3G3FV-PPGB2 or
3G3FV-PPGX2
1:1,000
150%/0 Hz
0.02%
Possible
Possible
Simple servo
drives
Precision speed
control
Torque control
Flux
Vector
3-19