Advanced Operation
The following diagram shows the relationship between each parameter and the output torque.
Reverse
Note When the torque limit function is engaged the torque control has priority and motor speed control
and compensation will be ignored, so the acceleration/deceleration times might be lengthened
and motor speed might be reduced.
H Limiting Torque with Analog Inputs
The following two analog inputs that can be used to limit torque.
Multi-function analog input terminal 16
Frequency reference (current) terminal 14
Use either or both of these inputs as needed with parameters H3-05 and H3-09. These parameters can-
not be changed during operation.
Parameter
Display name
p y
number
H3-05
Terminal 16 Sel
H3-09
Terminal 14 Sel
Settings
The following table shows only those settings related to the torque limit function.
Setting
10
Forward Torque Limit
11
Reverse Torque Limit
12
Regenerative Torque Limit
15
Speed Limit (Limits torque in both the forward and reverse directions.)
Set the analog input terminal's signal level, gain, and bias to match the actual input signal. The factory
default settings for the input terminal's signal level are as follows:
Terminal 16:
0 to 10 V (A 10-V input limits the torque to 100% of the motor's rated torque.)
Terminal 14:
4 to 20 mA (A 20-mA input limits the torque to 100% of the motor's rated torque.)
6-4
Output torque
L7-04
Regenerative
torque
L7-02
Setting
g
Units
Default
range
setting
0 to 1F
---
1F
1 to 1F
---
1F
Forward direction
L7-01
Motor speed
Regenerative
torque
L7-03
Reverse direction
Valid access levels
V/f
V/f with
Control
PG
Basic or Advanced
Advanced
Name
Chapter 6
Forward
Open Loop
Flux
Vector
Vector