Parameter Lists
H Carrier Frequency: C6
Name
Para
meter
meter
Display
No.
name
C6-01
Sets the carrier frequency
Carrier
frequency
upper limit and lower limit in
kHz units. (See note 2)
upper limit.
The carrier frequency
The carrier frequency
Carrier
proportional gain is set as
Freq Max
follows:
follows:
C6-02
Carrier
Note: In vector control mode,
frequency
lower limit.
Carrier
Freq Min
Carrier frequency
C6-03
C6-01
Carrier
frequency
C6-02
proportional
gain.
0
Carrier
Freq Gain
Note 1. The setting range and the default of the Inverter will differ depending on its capacity and con-
trol mode. (The value for the 200-V class 0.4 kW Inverter in open loop vector control mode is
given above.)
Note 2. For a 400-V Inverter, if the carrier frequency is set to a value higher than the default setting, the
Inverter overload "OL2" detection value will decrease.
H Hunting Prevention: C7
Name
Para
meter
meter
Display
No.
name
C7-01
0: Disabled
Hunting
prevention
1: Enabled
selection
Note: The hunting prevention
Hunt Prev
Select
C7-02
Sets the ratio for hunting
Hunting
prevention
prevention gain.
gain
Note: Usually setting is not nec-
Hunt Prev
Gain
Description
Setting
2.0 to
15.0
(
)
(see
(
note 1)
note 1)
0.4 to
15.0
the upper limit of the car-
(see
(
rier frequency is fixed at
q
y
note 1)
note 1)
C6 01
C6-01
0 to 99
Output frequency
(C6-03)
K
E1-04
(Max. frequency)
Output frequency
Description
Setting
0, 1
function is used to stop a
motor under a light load
from hunting.
This function is exclusive-
ly for the V/f control
ly for the V/f control
mode.
When greater responsive-
ness than vibration con-
trol is required, set hunt-
ing prevention to "dis-
abled."
0.00 to
2.50
essary.
Adjust in the following cir-
cumstances:
When vibration occurs
due to a light load, in-
due to a light load, in-
crease the set values.
When the motor is stalled,
decrease the set values.
If the set values become
too large, the motor may
stall as a result of non-
controlled current.
Default
Chan-
range
range
setting
setting
ges
ges
during
opera-
tion
15.0
NO
(see
note 1)
)
15.0
NO
(see
note 1)
)
0
NO
Default
Chan-
range
range
setting
setting
ges
ges
during
opera-
tion
1
NO
1.00
NO
Chapter 7
Control mode
V/f
V/f
Open
control
with
loop
PG
vector
B
B
B
A
A
X
A
A
X
Control mode
V/f
V/f
Open
control
with
loop
PG
vector
A
A
X
A
A
X
Page
Flux
vector
B
6-62
X
6-62
X
6-62
Page
Flux
vector
X
6-14,
6-38
X
6-14,
6-38
7-19