Advanced Operation
Note The above upper limit values are for 200-V class Inverters. Double the values for 400-V class
Inverters.
Output voltage (V)
Note 1. Set so that the following condition will be satisfied.
E1-06
E1-11
Note 2. The function is disabled if the parameters E-11 and E1-12 are both set to 0.0.
Note 3. If auto-tuning is executed, the parameters E1-05 and E1-13 will be set to the set voltage.
H Two-motor Switching Control Function
This function enables switching control between two motors using one Inverter. The following function
additions were made to support this new functionality.
Setting Control Mode and Motor Parameters for Second Motor
Set the following parameter for the second motor. The settings of parameters E1 and E2 are used for the
first motor.
If the motor is operated in flux or open-loop vector control mode, set the motor selection for auto-tuning
to 2.
Parameter
Display name
p y
number
E3-01
Control Method
Explanation of Settings
Setting
0
Normal V/f control
1
V/f control with PG
2
Open-loop vector control
3
Flux vector control
Set the control mode for the second motor. The set value will not be set to the default value when the
Inverter is initialized.
E1-04
Setting
g
Units
Default
range
setting
0 to 3
---
2
Valid access levels
V/f
V/f with
Control
PG
Advanced
Description
Chapter 6
Frequency (Hz)
Open Loop
Flux
Vector
Vector
6-67