Chapter 9. Specifications - Omron SYSDRIVE 3G3FV User Manual

High-function general-purpose inverter
Table of Contents

Advertisement

Maintenance Operations
S No dirt or dust should be accumulating on the heating fan unit.
S No dust should be accumulating on the vents.
S There should be no abnormalities in the outward appearance.
S The control panel cooling fan should be operating normally. (Check to be sure that there are no
unusual noises or vibration and that the accumulated operating time has not exceeded the specifi-
cations.)
Periodic Maintenance of Parts
The Inverter is configured of many parts, and these parts must be operating properly in order to
make full use of the Inverter's functions.
Among the electronic components, there are some that require maintenance depending on their
usage conditions. In order to keep the Inverter operating normally over a long period of time, it is
necessary to perform period inspections and replace parts according to their service life.
Periodic inspection standards vary depending the Inverter's installation environment and usage
conditions.
The Inverter's maintenance periods are noted below. Keep them as reference.
S Cooling fan:
S Electrolytic capacitor:
S Fuses:
The usage conditions are as follows:
S Ambient temperature
S Load factor:
S Operating time:
S Installation:
If the maintenance period is extended, it is recommended that the ambient temperature be lowered
and that the power-on time be reduced as much as possible.
Note For details regarding maintenance, consult your OMRON sales representative.
2 to 3 years
5 years
10 years
40 C
80%
8 hours per day
According to instructions in manual.
Chapter 8
8-23