Omron SYSDRIVE 3G3FV User Manual page 158

High-function general-purpose inverter
Table of Contents

Advertisement

Basic Operation
Note The voltage settings shown in parentheses are the values for the 400-V class.
H Motor Selection Setting (E1-02)
Set the motor selection (E1-02) to the type of motor to be used. This setting is used as a basis for motor
protection
Parameter
Display
p y
number
name
E1-02
Motor Selec-
tion
Setting
Setting
0
Standard fan-cooled motor (general-purpose motor)
1
Standard blower motor (inverter-exclusive motor)
2
Special motor (special vector control motor)
H Precautions Before Auto-tuning
Caution
Do not connect a load to the motor when performing auto-tuning. Doing so may re-
!
sult in personal injury or equipment damage.
The Inverter's auto-tuning function automatically determines the motor parameters while a servo sys-
tem's auto-tuning function determines the size of a load, so these auto-tuning functions are funda-
mentally different.
If a load is connected when auto-tuning is performed, not only will incorrect motor parameters be re-
corded, but the motor may operate erratically resulting in dangerous conditions such as loads falling
from vertical axis motors. Never perform auto-tuning with a load connected to the motor.
H Required Parameter Settings
Enter auto-tuning mode and make the following parameter settings:
Rated Voltage:
Rated Current:
Rated Frequency:
Rated Speed:
Number of poles:
Motor Selection:
PG Pulses/Rev:
The following message will appear when the parameters have been set:
Tuning Ready ?
Press RUN key
At this point, it is still possible to change the parameter settings by pressing the Increment and Decre-
ment Keys to display the desired parameter.
5-36
Setting
g
Units
range
0 to 2
---
Set the rated voltage (VAC) shown on the motor's nameplate.
Set the rated current (A) shown on the motor's nameplate.
Set the rated frequency (Hz) shown on the motor's nameplate.
Set the rated speed (r/min) shown on the motor's nameplate.
Set the number of poles.
Select motor 1.
For two-motor switching control, select motor 1 or motor 2.
Set the number of A-phase or B-phase pulses per revolution.
Valid access levels
Default
setting
V/f
V/f with
Control
PG
0
Quick-start
Function
Chapter 5
Open Loop
Flux
Vector
Vector