Preparing for Operation
H Example of Wiring for 3-wire Sequential Operation
Stop switch
Note 1. The default settings of the multi-function inputs are different from the default settings of the
2-wire sequence.
Note 2. When setting a 3-wire sequence, the operation can be started and stopped with an automati-
cally resetting pushbutton switch.
Initialization Example
The following example shows how to initialize parameters with the 2-wire sequence (factory settings).
Key sequence
3 times
S Write-protect Passwords
Use parameters A1-04 and A1-05 to write-protect the initialize-mode parameters. Parameters A1-01
through A1-03 and A2-01 through A2-32 can be displayed but not changed if the contents of A1-04 and
A1-05 don't match. These parameters cannot be changed during operation.
To write-protect the initialize-mode parameters, set the password in A1-05 after inputting the desired
values in A1-01 through A1-03 and A2-01 through A2-32. Parameter A1-05 can be displayed by dis-
playing A1-04 and pressing the Menu Key while pressing the Reset Key. (A1-05 can't be displayed with
the usual key sequences.)
It will be possible to change the initialize-mode parameters again when the password is written to
A1-04.
Run switch
(NO)
(NC)
Display
Run command
(Operates when the run switch is closed.)
Stop command
(Stops when the stop switch is open.)
5
Forward/Reverse rotation command
(Multi-function input 3)
11
Sequential input common
Displays operation mode.
Displays initialize mode.
Puts the Unit in initialize mode.
(Select Language display)
Displays the Initialize display.
Displays the parameter setting for A1-03.
Changes the setting to 2-wire Initialization.
Writes the new setting.
Returns to the Initialize display.
Chapter 3
Explanation
3-21