Advanced Operation
H Setting a Torque Limit with Parameters
Torque limits can be set separately for the 4 ways that torque can be applied: forward torque, reverse
torque, forward regenerative torque, and reverse forward regenerative torque. These parameters can-
not be changed during operation.
Parameter
Display name
p y
number
L7-01
Torque Limit Fwd
L7-02
Torque Limit Rev
L7-03
Torque Limit Fwd Rgn
L7-04
Torque Limit Rev Rgn
The following diagram shows the relationship between each parameter and the output torque.
Reverse
Note When the torque limit function is engaged the torque control has priority and motor speed control
and compensation will be ignored, so the acceleration/deceleration times might be lengthened
and motor speed might be reduced.
H Limiting Torque with Analog Inputs
The following two analog inputs that can be used to limit torque.
Multi-function analog input terminal 16
Frequency reference (current) terminal 14
Use either or both of these inputs as needed with parameters H3-05 and H3-09. These parameters can-
not be changed during operation.
Parameter
Display name
p y
number
H3-05
Terminal 16 Sel
H3-09
Terminal 14 Sel
Setting
g
Units Default
range
0 to 300
%
Output torque
L7-04
Regenerative
torque
L7-02
Setting
g
Units
Default
range
setting
0 to 1F
---
1F
1 to 1F
---
1F
Valid access levels
setting
V/f
V/f with
Control
PG
200
Not applicable
Forward direction
L7-01
Motor speed
Regenerative
torque
L7-03
Reverse direction
Valid access levels
V/f
V/f with
Control
PG
Basic or Advanced
Advanced
Chapter 6
Open Loop
Flux
Vector
Vector
Basic or Advanced
Forward
Open Loop
Flux
Vector
Vector
6-29