Basic Operation
Parameter
Display name
p y
number
H3-08
Term 14 Signal
Terminal 14 Signal Level Settings
Setting
Name
0
0 to 10 VDC
1
–10 to 10 VDC
2
4 to 20 mA
Note When the terminal is being used as a voltage input terminal (setting 0 or 1), jumper J1 must be
disconnected on the control board. (See the following diagram.) The terminal's input resistor will
be destroyed if the terminal is used for a voltage input with jumper J1 connected.
When frequency references are being input simultaneously from both the voltage terminal 13 and the
current terminal 14, the final reference value will be the sum of the two references that are input.
To switch the frequency reference input between the voltage terminal 13 and the current terminal 14,
set a value of 1F in any one of the multi-function inputs (H1-01 through H1-06). The voltage terminal 13
will be used when this multi-function input is OFF and the current terminal 14 will be used when this
multi-function input is ON.
The following diagram shows the location of jumper J1 on a 200-V Class, 0.4-kW Unit.
H Frequency Reference: Terminal 16 Voltage Input (H3-04 and H3-05)
This function is useful when switching between two analog inputs. When using this multi-function input
(terminal 16) as the frequency reference terminal, first set the multi-function analog input's function to
"Auxiliary Reference" by setting parameter H3-05 to "0." (Neither H3-04 nor H3-05 can be changed dur-
ing operation.)
5-6
Setting
g
Units
range
0 to 2
---
2
0 to 10 VDC input
–10 to 10 VDC input
(A negative voltage is a command for rotation in the opposite direction.)
4 to 20 mA input
Jumper wire
Valid access levels
Default
setting
V/f
V/f with
Control
Advanced
Function
Chapter 5
Open Loop
PG
Vector
Control
circuit
terminals
Main circuit
terminals
Flux
Vector