PROBLEM
Heat Will Not Turn On.
Inadequate Heating.
Heat Will Not Turn Off.

Phase Loss Protection

The phase loss protection option will monitor the three-phase elec-
trical system to provide phase reversal and phase loss protection.

PHASE REVERSAL PROTECTION

If the control senses an incorrect phase relationship, the relay
(K1) will be de-energized (opening its contact). If the phase re-
lationship is correct, the relay will be energized. The control
has a self-bypass function after a pre-set time. If the control de-
termines that the three phases stay in a correct relationship for
10 consecutive minutes, the relay will stay energized regard-
less of the phase sequence of three inputs as long as 24-vac
control voltage is applied. This self-bypass function will be re-
set if all three phases are restored in a phase loss event.
PHASE LOSS PROTECTION
If the reverse rotation board senses any one of the three phase
inputs has no AC voltage, the relay will be de-energized (open-
ing its contact). This protection is always active as long as 24-
vac control voltage is applied, and is not affected by the self
by-pass function of the phase sequence monitoring function.
However, in the event of phase loss, the relay will be re-ener-
gized only if all three phases are restored and the three phases
are in the correct sequence.
A red LED is provided to indicate the function of the board.
See the following table.
Table 21 — Electric Heat Service Analysis
CAUSE
Active alarm.
Unit is NOT configured for heat.
No power to unit.
Unit is in minimum heat off-time, or minimum
cool-heat changeover time.
Thermostat or occupancy schedule setpoint not
calling for heating.
Heat forced off in Service Test mode.
No 24 vac at heater contactor.
Open temperature limit switch on heater.
Dirty air filters.
Thermostat or occupancy schedule setpoint only
calling for W1
Heat undersized for load.
Restricted airflow
Too much outdoor air.
Limit switch cycles heaters.
Bad heater elements.
Unit is in minimum heat on-time.
Thermostat or occupancy schedule setpoint still
calling for heating.
Heat forced on in Service Test mode.
Heater contactor failed.
57
Check active alarms using ComfortLink scrolling
marquee.
Check heating configurations using the
ComfortLink scrolling marquee
Check power supply, fuses, wiring, and circuit
breakers.
Check using ComfortLink scrolling marquee.
Check using ComfortLink scrolling marquee.
Check using ComfortLink scrolling marquee.
Turn Service Test mode off.
Check transformer and circuit breaker.
Check auto-reset limit switches on heater.
Check manual-reset limit switch (LS) on indoor
fan housing.
Check minimum airflow. Check limit switch when
it is cool, replace if open.
Replace air filters.
Allow time for W2 to energize or adjust setpoints.
Decrease load or increase size of heater.
Remove restriction. Check SAT compared to the
SAT heating limits.
Check economizer position and configuration.
Adjust minimum position.
Check rotation of blower and minimum airflow.
Power off unit and remove high voltage wires.
Check resistance of element, replace if open.
Check using ComfortLink scrolling marquee.
Check using ComfortLink scrolling marquee.
Check using ComfortLink scrolling marquee.
Turn Service Test mode off.
Power off unit. Check contactor and replace if
closed.
LED STATUS
On Continuously Relay contact closed (normal operation).
Relay contact open (phase loss or phase
Blinking
reversal has occurred) — No power will be
supplied to the control system.
Off
24 vac control power not present (off).

Thermistor Troubleshooting

The electronic control uses thermistors to sense temperatures
used to control operation of the unit. Resistances at various
temperatures are listed in Tables 22 and 23. Thermistor pin
connection points are shown in the Major System Components
section. The general locations of the thermistors are shown the
Major System Components section.

AIR TEMPERATURES

Air temperatures are measured with 10 kilo-ohm thermistors.
This includes supply-air temperature (SAT), outdoor-air tem-
perature (OAT), space temperature sensors (T55, T56, T58),
and return air temperature (RAT).
The supply air temperature (SAT) and outdoor air temperature
(OAT) thermistors use a snap-mount to attach through the unit
sheet metal panels. The snap-mount tabs must be flattened on
the tip end of the sensor to release for removal from the panel.
(See Fig. 18.) To reinstall, make sure the snap-mount tabs ex-
tend out.
REMEDY