Electrical Data; Voltage Range; Outdoor Fan Motor - Carrier 40KMC Installation Instructions Manual

In-ceiling cassette duct-free split system
Hide thumbs Also See for 40KMC:
Table of Contents

Advertisement

ELECTRICAL DATA
Table 10 —38HDF/38QRF Electrical Data
COMPRESSOR
OUTDOOR FAN MOTOR
FUSE/
38HDF/38QRF
V-PH-Hz
VOLTAGE RANGE*
MIN CKT
CKT
UNIT SIZE
ven
AMPS
BKR
Min
Max
RLA
LRA
FLA
NEC
Hp
kW Out
AMPS
018
208/230 —1-60
187
253
9.0
48.0
0.80
0.125
0.09
12.4
20
024
208/230 —1-60
187
253
12.8
58.3
0.80
0.125
0.09
16.8
25
38QRF030
208/230 —1-60
187
253
14.4
73.0
1.50
0.25
0.19
18.4
30
38HDFO30
208/230 —1-60
187
253
14.4
73.0
0.80
0.125
0.09
18.4
30
208/230 —1-60
187
253
16.7
79.0
1.50
0.25
0.19
22.3
35
035
208/230-3-60
187
253
10.4
73.0
1.50
0.25
0.19
14.5
20
460—-3-—60
414
506
5.8
38.0
0.80
0.25
0.19
8.7
15
208/230 —1-60
187
253
17.9
112.0
1.45
0.25
0.19
23.8
40
036
208/230-3-60
187
253
13.2
88.0
1.45
0.25
0.19
18.0
30
460—-3-—60
414
506
6.0
44.0
0.80
0.25
0.19
8.3
15
Table 11 — 40K MC
Fan coil Electrical Data
Voltage Range
FAN
Power
Louver
40KMC
Condensate
FUSE/
e e
V-PH-Hz
Motor
Unit Size
:
Pump FLA
MIN CKT
CKT
Min.
Max
FLA
Watts
FLA
AMPS
BKR
AMPS
018
208/230—1—60
187
253
0.55
120
0.08
0.01
0.8
15
024
208/230 —1-60
187
253
0.50
110
0.06
0.01
0.7
15
030
208/230 —1-60
187
253
0.95
210
0.06
0.01
1.3
15
036
208/230 —1-60
187
253
0.95
210
0.06
0.01
1.3
15
Table 12 —- 40KMQ Fan Coil Electrical Data
Voltage
FAN
Electric
Power
Range
L
Heaters
ouver
40KMQ
Condensate
FUSE/
Unit Size
V-PH-Hz
Motor | Pump FLA
Motor
MIN
CKT
Min. | Max |
FLA | Power
FLA
kw
FLA
CKT
BKR
(Watts)
AMPS
| anaps
018
208/230 —1-60
187
253
0.50
110
0.06
0.01
3
12.5
16.3
20
024
208/230 —1-60
187
253
0.50
110
0.06
0.01
3
12.5
16.3
20
030
208/230 —1-60
187
253
0.95
210
0.06
0.01
3
12.5
16.9
20
036
208/230 —1-60
187
253
0.95
210
0.06
0.01
3
12.5
16.9
20
*Permissible limits of the voltage range at which unit will operate satisfactorily.
LEGEND
NOTES:
FLA
-
MCA
-
NEC
-
RLA
-
Full Load Amps
Minimum
Circuit Amps per NEC Section 430-24
National Electrical Code
Rated Load Amps
(Compressor)
1. In compliance with NEC requirements for multi-motor and combination
load equipment (refer to NEC Articles 430 and 440), the over—current
protective device for the unit shall be fuse or equipped with a breaker.
2. Motor RLA values are established in accordance with UL (Underwriters
Laboratories) Standard 465.