Srx210 Services Gateway Rack Requirements; Clearance Requirements For Airflow And Hardware Maintenance Of The Srx210 - Juniper SRX210 - HARDWARE GUIDE REV 3 Hardware Manual

Services gateway
Hide thumbs Also See for SRX210 - HARDWARE GUIDE REV 3:
Table of Contents

Advertisement

SRX210 Services Gateway Hardware Guide
Related
Documentation

SRX210 Services Gateway Rack Requirements

52
Table 21: SRX210 Services Gateway Cabinet Requirements
Cabinet
Requirements
Specifications
Cabinet size
19 in. (48.3 cm) as defined in Cabinets, Racks, Panels, and Associated
Equipment (document number EIA-310–D) published by the Electronics
Industry Association (
You can mount the services gateway horizontally in the cabinet.
Clearance
The cabinet is at least 1 U (1.75 in. or 4.5 cm) high.
requirements
The outer edges of the mounting brackets extend the width of either chassis
to 19 in. (48.2 cm), and the front of the chassis extends approximately 0.5
in. (1.27 cm) beyond the mounting brackets.
The minimum total clearance inside the cabinet is 30.7 in. (78 cm) between
the inside of the front door and the inside of the rear door.
NOTE: The holes for the mounting brackets chassis are spaced 1.25 in. (3.2
cm) apart, measured from the center of the hole.
Cabinet airflow
Ensure sufficient ventilation through the cabinet is sufficient to prevent
requirements
overheating.
Ensure adequate cool air supply to dissipate the thermal output of the
device.
Install the device as close as possible to the front of the cabinet so that
the cable management system clears the inside of the front door. Installing
the chassis close to the front of the cabinet maximizes the clearance in
the rear of the cabinet for critical airflow.
Route and dress all cables to minimize the blockage of airflow to and from
the chassis.
NOTE: A cabinet larger than the minimum required provides better airflow
and reduces the chance of overheating.
General Site Guidelines for Installing the SRX210 Services Gateway on page 51
Site Preparation Checklist for the SRX210 Services Gateway on page 49
SRX210 Services Gateway Rack Requirements on page 52
Clearance Requirements for Airflow and Hardware Maintenance of the SRX210 Services
Gateway on page 53
The services gateway can be installed in a rack. Many types of racks are acceptable,
including front-mount racks and four-post (telco) racks.
NOTE: The services gateway cannot be center-mounted in racks.
Table 22 on page 53 provides the details on rack size, clearance, and airflow requirements.
http://www.eia.org
).
Copyright © 2010, Juniper Networks, Inc.