Disconnect / Re-Connect Com Loop; Test Mode; Test Alarm Devices; Test Of Routing Equipment - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
13.13.9
13.14
13.15
13.16

Disconnect / Re-connect COM loop

Disconnect the COM loop via menu H5/A1. Disconnected COM loop
will stay disconnected until re-connected.
Re-connect via menu H5/A1.
For more information see EBL128 Operating Instructions.

Test mode

Up to four zones can be set in Test mode at the same time.
points / zones can be tested during the Monthly test (via menu H1) or
separately (via menu H7). For more information see the EBL128
Operating Instructions. The LED "Test mode" indicates one or more
zones in Test mode. Zones in Test mode are also simultaneously
shown in the EBL128 display.
any time delay for the detectors / zones in test mode will be
"disabled", i.e. fire alarm will be activated faster than normally.

Test alarm devices

The programmable outputs type "Alarm device" can be collectively
activated via menu H8/S3, which make it possible to test the alarm
devices.
(The test can not be started if a fire alarm already is
activated.) When the test starts the alarm devices will be turned "ON"
for 5 seconds (±1s), "off" for 25 seconds (±1s), "on" for 5 seconds and
107
so on.
NOTE! Also disabled (and silenced) alarm devices will be tested.
The test will continue for one hour if it is not stopped via menu H8/S3
or if a fire alarm is activated in the system.

Test of routing equipment

Via menu H1 it is possible to test the fault and fire alarm outputs for
routing equipment (Fault tx & Fire brigade tx).
In menu H1, press "Accept" to start the test. The fault output will be
108
activated
, indicated by LED "Fault tx activated". After 30 seconds
will also the fire output be activated, indicated by LED "Fire brigade
tx". After additional 30 seconds will the test be ended and the outputs
and LEDs will go back to "normal" status.
105
In DBI (Danish) convention, one zone only.
106
Disablements, faults and fire alarms have higher priority, i.e. the
presentation of zones in Test mode will be suppressed during such a
condition.
107
The output activation will be continuously (steady).
devices 3377 and 3378, the tone with the highest priority level (and type
"alarm device") will be automatically selected.
108
NOTE! The Fault tx output is activated in "normal" state, i.e. it will in
this test be de-activated.
EBL128 Planning Instructions V1.1.x
106
In order to shorten the testing time,
98
105
Alarm
For the alarm