Disable / re-enable outputs for routing
equipment (B10)
Not available for users with access level / type "Information only".
Disabled outputs for routing equipment are listed in menu H4/U1.
Outputs for routing equipment (fire brigade tx / fault tx) can be
disabled and re-enabled via this menu (B10). Disabled output will
stay disabled, until re-enabled again via this menu.
Can be useful during an installation and test period, when only local
alarms are required.
Disabled output for routing equipment is also indicated by LED
"Fault / Disablements Fire brigade tx" (L15).
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press "2") to menu H2.
H2 Disable or re-enable
Press "A" to sub menu B1.
B1 Disable zone
Scroll (or press "0") to menu B10.
B10 Disable / re-enable outputs for routing equipment
Press "A".
The actual status for the output FIRE and FAULT respectively will be
shown. Use the keypad to select:
1=enabled
or
0=disabled
for the output respectively.
Step right / left with the arrow keys.
Press "A". The new status for the output FIRE and FAULT
respectively will be shown.
Press "A" and "Return" (P9) to menu B10.
Scroll to another menu or press "Return" to menu H2. Scroll to
another menu or leave the menu system by pressing "Return".