All addressable alarm points (also addressable manual call points),
connected to the COM loop, can be individually disabled.
Disabled alarm points (zone – address) are listed in menu H4/U1.
Disabled alarm points (zone – address) can be automatically re-
enabled or they have to be re-enabled via menu H2/B6.
Text in display
Disable or re-enable
Disable zone
Disable zone / address
Disable zone: 00 Address: 00
Disable zone: 01 Address: 01
Automatic re-enabling:0 (0=No,1=Yes)
Time: HH:MM
(Default is current time + 3 hours)
Disable zone: 00 Address: 00
EBL128 Operating Instructions V1.1.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B2
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
83
Comments
According to chapter
"Access", see page 78.
Press "A" to accept.
Press "1" for aut. re-
enabling and accept or
change the time (max. 24
hours). Press "A" to
accept. LED
"Disablements" (L8) will
light up.
If more disablements
shall be done, continue
like above. If not, press
"Return" to menu B2.
Scroll or press "Return"
to menu H2. Scroll or
press "Return" to log off.