Multi-function Input Operation Selection

The multi-function input terminals can be set to either NO (NO contact) or NC (NC contact) individually.
This manual describes each function with the Multi-function Input 1 to 7 Operation Selection (C011 to
C017) set to 00 (NO: NO contact). Note that the operations of set signals are reversed when you set
them to 01 (NC: NC contact).
Parameter
No.
Multi-function Input 1 Operation
C011
Selection
Multi-function Input 2 Operation
C012
Selection
Multi-function Input 3 Operation
C013
Selection
Multi-function Input 4 Operation
C014
Selection
Multi-function Input 5 Operation
C015
Selection
Multi-function Input 6 Operation
C016
Selection
Multi-function Input 7 Operation
C017
Selection
Related functions
*1. NO contact: ON when closed, OFF when open
NC contact: ON when open, OFF when closed
5-9-3

Input Terminal Response Time

• Set the response time for each multi-function input 1 to 7 terminal independently.
This function is effective for removing noise caused by chattering etc.
• If the terminal input becomes unstable because of chattering, increase the set value.
However, increasing the set value results in a slow response.
The setting range is 0 to 200, which provides a response time of approximately 2 to 400 ms.
Parameter
No.
C160 to
Multi-function Input 1 to 7
C166
Response Time
*1. When 0 is set, the response time is 2 ms.
5-9-4

Forward RUN Command (FW) and Reverse RUN Command (RV)

• To input the forward and reverse RUN commands via the control circuit terminals, set the Multi-func-
tion Input 1 to 7 Selection (C001 to C007) to 00 (FW) and 01 (RV).
• By default, the Multi-function Input 1 Selection (C001) is set to 00 (FW) and the Multi-function Input 2
Selection (C002) is set to 01 (RV), respectively.
• To input the RUN command via these control circuit terminals, set the 1st/2nd RUN Command Selec-
tion (A002/A202) to 01 (Control circuit terminal block).
• If the terminals FW and RV turn ON simultaneously, the inverter will stop without displaying any
alarm. It will start operating again when either of these terminals turns OFF.
Parameter
No.
Multi-function Input 1 to 7 Selection 00:
C001 to
C007
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Function name
00:
01:
• Each multi-function input termi-
• The terminal allocated to 18 (RS:
C001 to C007
Function name
0. to 200. ( 2 ms)
Function name
01:
Data
NO (NO contact)
NC (NC contact)
nal 1 to 7 can be set indepen-
dently to either an NO contact or
*1
NC contact input terminal.
Reset) cannot be set to NC
contact. Be sure to set the NO
contact.
Data
*1
Data
FW (Forward)
RV (Reverse)
5 Basic Settings
Default
Unit
data
00
Default
Unit
data
1.
ms
Default
Unit
data
5 - 47
5