CH1 Heating control output cycle setting
Set the pulse cycle (ON/OFF cycle) of the transistor output.
The ON time of the control output cycle is determined by multiplying the control output cycle by the manipulated value for
heating (MVh) (%) calculated by a PID operation. When the manipulated value for heating (MVh) is stable, pulses are
repeatedly output in the same cycle. For details on this area, refer to the following:
Page 261 CH1 Control output cycle setting
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Heating control output cycle setting
CH Heating control output cycle setting (in the Q compatible mode)
CH1 Control response parameter
In the simple two-degree-of-freedom PID control, select the response speed to the change of the set value (SV) from the
following three levels: Slow, Normal, and Fast.
For details on the simple two-degree-of-freedom, refer to the following:
Page 56 Simple Two-degree-of-freedom
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Control response parameter
CH Control response parameter (in the Q compatible mode)
APPX
262
Appendix 3 Buffer Memory Areas
CH1
CH2
504
704
47
79
CH1
CH2
505
705
49
81
CH3
CH4
904
1104
111
143
CH3
CH4
905
1105
113
145