CT1 CT selection [Q compatible mode]
Select the current sensor (CT) to be connected to CT1 in the Q compatible mode.
■Setting range
• 0: CTL-12-S36-8 (0.0 to 100.0A)
• 1: CTL-6-P(-H) (0.00 to 20.00A)
• 2: CT ratio setting (0.0 to 100.0A)
■Correspondence between each CT input terminal and buffer memory address
CT input terminal
CT1
CT2
CT3
CT4
CT5
CT6
CT7
CT8
■Setting current sensors (CT) and buffer memory areas
When using a current sensor (CT) other than the CTL-12-S36-8 and CTL-6-P(-H), set the number of second-winding (turns) of
the current sensor (CT) to be connected in 'CT1 CT ratio setting' (in the Q compatible mode) (Un\G288). Set the following
buffer memory areas as follows according to the specifications of the current sensor (CT) to be used:
Current sensor (CT) to be used
Products of
CTL-12-S36-8
U.R.D.Co., LTD.
CTL-6-P
www.u-rd.com
CTL-6-P-H
CTL-12-S36-10
CTL-12-S56-10
Other current sensors (CT)
• When using the CTL-12-L-8 current sensor (CT), set CTL-12-S36-8 (0.0 to 100.0A) (0).
• When using the CTL-6-S-H current sensor (CT), set CTL-6-P(-H) (0.00 to 20.00A) (1).
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
APPX
322
Appendix 3 Buffer Memory Areas
'CT1 CT selection' (in the Q
compatible mode) (Un\G272)
CTL-12-S36-8 (0.0 to 100.0A) (0)
CTL-6-P(-H) (0.00 to 20.00A) (1)
CTL-6-P(-H) (0.00 to 20.00A) (1)
CT ratio setting (0.0 to 100.0A) (2)
CT ratio setting (0.0 to 100.0A) (2)
CT ratio setting (0.0 to 100.0A) (2)
Buffer memory address
272
273
274
275
276
277
278
279
'CT1 CT ratio setting' (in the Q
compatible mode) (Un\G288)
Setting not required
Setting not required
Setting not required
Set 1000, which is the number of second-
winding (turns).
Set 1000, which is the number of second-
winding (turns).
Set the number of second-winding (turns)
depending on the specifications of the
current sensor (CT) used.
Remarks
The production has
stopped, but these
products can be used.
Current sensors (CT)
whose number of
secondwinding (turns) is
600 to 9999 can be used.